CE Marked motorised model
Multi blade damper for thin profile
Blades remain in casing
Tested according to the test standard EN-1366-2
Fire class: E 60 S / E 120
Tested 10000 (open/close)
Sizes from 200 x 200 mm to 1200 x 1200 mm
Tested in installations for gypsum walls (max size 800 x 800) and for solid walls and floors
The fire damper casing tightness class B according to EN 1751
The fire damper fulfills the requirements of tightness class 2 according to EN 1751
Damper can be installed in horizontal or vertical position Equipped with slip or flange joint
ETPS-E is a rectangular fire damper equipped with an actuator and CE marked based on product standard EN 15650:2010. The damper fulfils the requirements of fire class E 60 / E 90 / E 120. The damper is installed in the ventilation duct between fire compartments to stop the spread of flue gases.
If the fire damper is installed in a construction element with fire class EI, the ductwork
must be equipped with fire insulation and safety distances must be observed. In this way,
also the spread of fire can be prevented. If the fire damper is installed in a construction
element with fire class E, no fire insulation is required in the duct, and no safety distances
need to be preserved.
When the fire damper is used to prevent the spread of fire and flue gases, it has to close
after it has received a signal from the smoke detector which is located in the duct or other
suitable location.
• The fire damper is open during normal ventilation.
• When the smoke detector detects smoke, the power supply to the actuator is interrupted and the damper closes automatically.