K6 active closed climate beam for various ceiling types.The casing is made of galvanized sheet steel, powder coated, with a perforated front plate with circular perforations. Casing manufactured from galvanized sheet steel with connection diameter of 125 mm. The heat exchanger has aluminium fins and a copper collector with a Ø 15 mm connection. The K6 climate beam is Eurovent certified.
Ceiling
Suspended ceiling
2 way throw
Rectangular execution
Adjustable
Easy access
Airflow direction Horizontal
Airflow type Supply
Installation height <3,5 m
Min. length climate beam 600 mm
Max. length climate beam 3000 mm
Available steps in length 100 mm (other steps on request)
Height 210 mm
Casing Galvanised steel plate, powder coated
Plenum box Galvanised steel plate
Door Perforated galvanised steel plate / Rotating in 2 directions, removable
Deflection vanes (optional) Plastic / +/- 40° adjustable with steps of 10°
Pressure measuring point Silicone
Heat exchanger Cu / Al
Standard finishing RAL9010
Air side Ø 125 mm (2 air inlets recommended for primary airflow rates larger than 140 m³/h)
Water side Ø 15 mm
Rail with mounting straps 4 per beam
Certification Eurovent Chilled Beams
Minimum primary pressure 50 Pa
A chilled beam is an on convection based HVAC system.
The K6 chilled beam is a high-performance, active and
closed chilled beam able to both cool and heat room air.
This air is subsequently mixed with fresh, primary air in
order to finally be blown back into the room.