Automatic exhaust valves type ATVC-100 are suitable for installations in multi-storey residential buildings, office blocks, hotels, schools etc., with a central exhaust air system. ATVC-100 can be installed either in new or renovated buildings.
Application
Automatic exhaust valves type ATVC-100 are suitable for installations in multi-storey residential buildings, office blocks,
hotels, schools etc., with a central exhaust air system. ATVC100 can be installed either in new or renovated buildings.
Realisation
The automatic exhaust valve is an air control unit controlled
by an electric pilot switch. It is normally closed or slightly
open to alow a basic air flow rate. Air is extracted at a higher
operating rate only when the switch contact is closed.
Operating
When the circuit is closed, the electro-thermal drive heats up
and causes the valve disc to open within 2 to 4 minutes
(delay desirable during a brief stay in the room). Air is
exhausted through the opening between the valve housing
and the valve disc. The valve stroke (6 mm) is always the
same, that is, the valve disc always moves from the minimum
setting up to the maximum valve opening. In the minimum
setting, the valve disc can either be closed or opened. Since
the valve stroke is always the same, the operating air flow
rate depends on the minimum setting and cannot be freely
selected. After the interruption of the circuit, the valve
remains open for after-ventilation for approx. 5 - 8 minutes
before it starts to move back to its minimum setting slowly
and silently.