The 62X Series dedicated outdoor air unit utilizes variable capacity compressors on the lead circuit and efficient scroll compressors on the lag circuit, that have been optimally designed for use with Puron® refrigerant (R410A). Operating efficiency of the units may be increased by adding the optional energy recovery system. The 62X Series units are designed to meet customer requirements for ventilation air applications. All 62X units include a factory installed and programmed BACnet controller, capable of standalone operation or integration into a building automation system.
Puron® non-ozone depleting R-410A refrigerant
High-efficiency scroll compressors on lag circuit
Variable capacity compressor on lead circuit
Direct drive plenum fans
TXV (thermostatic expansion valve) refrigerant metering device for each circuit
Cooling operation range from 35 F to 115 F ambient
24-v control circuit
Rubber fan vibration isolators
2-in. double wall construction with an R-13 rating
Sloped, insulated, stainless steel condensate pan
Dual filter rank assembly with 2-in. pre-filter and 4-in. secondary filter
Direct drive motors
High-efficiency 1 HP and larger motors meet EPACT (Energy Policy Act)
Two-position outside air damper on 100% outdoor air units
Closed when fan is off
Microprocessor control:
Easy to use BACview handheld keypad/display accessory
Closed when fan is off
Occupancy schedule
Service diagnostics
Alarms and alarm history
Short-cycle compressor protection
Supports communications with BACnet™, Modbus, and LonWorks® controls
Remote start/stop capability
Dual electrically and mechanically independent refrigeration circuits (unit sizes 12-55)
Crankcase heaters