Carrier’s ComfortVu™ BACnet thermostats offer local control of a building’s heating, ventilating and air-conditioning (HVAC) system as well as remote control from any BACnet-compliant building management system (BMS), including Carrier’s i-Vu® building automation system.
Large, backlit LCD display
Touchscreen occupant controls
Support for Celcius or Fahrenheit
BACnet MS/TP port for easy integration with i-Vu system or any BACnet-compliant BMS
On-board DIP switches to configure equipment type and sequence of operation
2 universal inputs, 2 analog outputs, and 6 digital outputs
Available in one 120/220 Vac model (international only, not UL approved):
Temperature/Humidity (TBPL-H-C)
Manage 7-day schedules via the thermostat
Manage setpoints, occupancy status, fan speed, and heating/cooling mode via the thermostat or BACnet BMS
Support for Title 24 demand response/economizer FDD and IECC2015 economizer FDD when connected to a BMS
Rooftop Units
Heat Pumps
Fan Coils
Exhaust Fans
Unit Heaters
Up to 3 stages of heat / 2 stages of cool
2 pipe / 4 pipe cooling / heating valves (0-10V)
Up to 3 fan speeds
VFD (0-10V)
Economizer (open/close)
Reversing valve
Humidifier (0-10V) / Reheat (dehumidify)
Power Requirements - 85-240 Vac line voltage: 1.5VA unit, 920 VA full load
Communication - BACnet MS/TP with baud rates up to 76.8 kbps, detected and set automatically by the BACnet Thermostat. Max 127 devices.
Real-time Clock - Real-time clock keeps track of time in the event of a power failure for up to 7 days
Display - Backlit Touchscreen, °F or °C Selectable
Sensing Element - Temperature: Range: 41° F to 95° F (5° C to 35° C) Accuracy: ±1.0° F (0.5° C)