To actively detect gas and control gas valves / alarms.
The detector generates an alarm and cuts the gas supply OFF when an excessive concentration of explosive gases in the air is detected by sensors hooked up to the detector central unit. The unit may cooperate with up to two gas sensors. The detector may cooperate with a gas cut-off valve activated by an electrical pulse or with a valve electrically held up in the open position. May also control a fan.
Device controlled
fan, gas cut-off valve, alarm circuitry
Power supply
230 V 50 Hz
Number of gas sensors
2
Gas sensor type
4…20 mA linear current loop corresponding to 0…20 % LEL (Lower Explosion Limit)
Alarm threshold
20,3 mA ± 2 %
Fuse
1 A (slow)
Fan outputvoltage-free NO contacts (rated load 3 A 230 V 50 Hz)
Alarm output
12 VDC, rated load
1 A
Electrically held gas valve output
12 VDC, rated load 1.3 A (16 W)
Pulse-activated gas valve output
12 VDC, rated load 5 A
Status visualization
LED diodes
Operating temperature range
+5 °C…+35 °C
Storage temperature range
0 °C…+60 °C
IP rating
IP 22, class II protection against electric shocks
Colour
gray
Mount method
wall-mounted, wall plugs
Weight
1.75 kg
Certificates/standards
complies with the EMC and LVD Directives, and with the PN-EN50194:2005 standard
Warranty period
2 years
Dimensions (W/H/D) mm
235/210/120
Packing list
Euroster CG2 monitor/controller, instructions