-Signalling of escape routes with pictogram and LED source.
-Ceiling/wall/vertical flag on wall installation without accessories. Polycarbonate component support structure with a white finish.
-Two-sided transparent luminous screen to which 1 or 2 pictograms can be applied. Kit of pictograms supplied.
-Models for 26 m sign visibility distance (compliance with EN 1838 and ISO 7010). Models for 32 m sign visibility distance for large spaces.
-Permanent (SA) or non-permanent (SE) operation: cinema/theater mode with brightness reduction to 50%. 3h emergency autonomy (24h recharge, 12h for 2h autonomy).
-Latest generation LiFePO4 (Lithium- Iron-Phosphate) battery ensuring more stable performance over time and better environmental compatibility (nickel and cadmium free). Self-test.
-Multi-colour LED indicator signalling correct operation or any faults. Local test by acting on a button outside the body.
-Local test of lamp function using a standard laser pointer to perform the operation from the ground.
-An accessory kit with additional pictograms for special messages is available.
-Accessories available on request control unit for luminaires with centralised testing and signalling. Inhibition function.