Wall-mounted convector heaters with smooth front panelling and rounded edges will prove an excellent addition to both modern and historic interiors as well as to environments with increased safety requirements.
Convection heating is especially suitable for settings where prompt response to temperature fl uctuations and low surface temperature are required. For a clean look, select a heater-to-wall connection option.
Schools, preschools
Hospitals, retirement homes
Institutions for people with reduced mobility
Family houses
Entrance areas, lobbies
Shopping malls, airport lounges
Hotels
Radiator with printed motif!
Radiators in your style! Designer radiators with the possibility of direct printing. Select from our motif selection or choose your own design or photograph.
Standard Equipment
Cover surface-treated steel sheet metal with an epoxy polyester powder coating
Grille round or rectangular holes as per order speci cations; grille is securely attached to the cover
Heat-exchanger Al-Cu lamellar heat-exchanger with a air vent valve, 2 × G1/2” inner connection threads
Valve axial thermostatic valve, M30 x 1.5 thread with a 2.5 mm pitch (not supplied with side connection
con guration)
Mounting wall brackets with connecting elements
Operating Conditions
Max. operating temp. 110°C
Max. operating excess
pressure
1 MPa (10 bar)
Protection IP20
Ambient conditions temperature T = +2 to +40°C
humidity Rh = 20 to 70%
Heating output of the convector TSK 0200 0122 2000 for temperature gradient 70/55°C
1. Output 75/65/20 ° C = 1 234 W
2. Factor from the table for 70/55/20 ° C at 122 width: f = 0.797
3. Output 70/55/20 ° C = f x 1 234 = 983 W