Variable flow damper
Variable or constant flow regulation
Rapid access to readings via the controller display
Quick setting of parameters
Analogue controls or Modbus control
Can be easily anti-condensation insulated in the duct system
Variants:
Circular connections: Ø100-630 mm
Rectangular connections: 200x200-1400x700 mm
Available with spring return actuator
Technical description
General
• Intended for flow regulation of comfort ventilation.
• Moist, cold and aggressive environments must be
avoided.
• Can be installed in both supply and extract air systems.
• Pressure-independent, but does require a minimum
pressure drop of 10 Pa across the damper.
• The minimum air flow must be considered during
design.
• For good regulation, a minimum difference between
Vmin and Vmax of 20% of the product’s Vnom is
recommended.
Design
• Motor: Normal or spring return.
• Options for selection of spring return (Order item):
– Normally closed (NC).
– Normally open (NO).
• Integrated air flow sensor.
• Analogue controls 0(2)-10 V or Modbus control.
Circular variant:
• Connection: Ø100-630 mm.
• Always supplied with dust protection.
• Motor shelf with 30 mm spacer to facilitate condensation
insulation of the duct system.
• A factory-insulated model available on request.
Rectangular variant:
• Connection 200x200-1400x700 mm.
• Other sizes are also available on request.
Functions
• Variable or constant flow regulation.
• Measurement of air flow.
• Display for direct reading.
• Settings can be made directly on the controller with
the help of a screwdriver.
Materials and surface treatment
• All sheet-metal parts are galvanized sheet steel (Z275).
• Measuring rods are aluminium.