Analogue clock thermostat with a low profile design for time-dependent monitoring and control of room temperature
Mains version
Tappet program disc with daily program
Synchronous motor drive
Normal temperature can be set
Reduced temperature approx. 5 K lower in relation to the set comfort temperature
Without selector switch
Electronic temperature control
Operating point and electronic recirculation are set from the front
Party switch and program display
Electronic temperature control
Selector switch for operating mode: con-tinuous reduced temperature, continuous normal temperature, automatic mode, frost and plant protection +6 °C
Operating voltage - 230 V AC
Frequency - 50 Hz
Type of contact - Changeover contact
Installation type - Wall installation
Program - Daily program
Switching capacity - 6 A at 250 V AC, cos φ = 1, 1 A at 250 V AC, cos φ = 0.6
Switching differential - 1.5 K
Switching output - Potential-free, not for SELV
Suitable for SELV - No
Setting range temperature - 10°C ... 30°C
Shortest switching times - 20 min
Programmable every - 5 min
Time accuracy at 25 °C - Synchronised with mains
Stand-by consumption - ~1.3 W
Display - 1 LED Heizen
Colour - White
Type of protection - IP 20
Protection class - II according to EN 60 730-1