For measuring the carbon dioxide concentration in the air (air quality) and, if necessary, for controlling the ventilation function
Operating voltage: 24 V DC (± 5 %)
Measuring range: 0 – 3000 ppm CO2
Impulse duration: 3.5 s
Contact design: 2 x closers, max. 230 V, 0.5 A
Protection class: IP30
Surface-mounted plastic housing, white (W x H x D): 78 x 78 x 35 mm
Area of application: Smoke and heat exhaust ventilation systems (RWA)
Product type: Accessories
Operating voltage: 24 V
Application: Staircase (smoke ventilation acc. to MBO/LBO), Miscellaneous (smoke exhaust to EN 12101-2)