Circular fire dampers, KOOLAIR, model SCFC-PD, S/UNE-EN 1366-2:2000 EI-120 (ve i↔o) and (ho i↔o). Fire resistence 2 hours. Rectangular fire damper class EI-120.
Dimensions from Ø 100 to Ø 355 mm.
The housing is composed of a single body of steel
sheet with an innercutout reinforced by a slotted
perforated frame that eliminates completely the
thermal bridge.
The dampers are closed when the thermal fuse blows
or trips at temperatures above 70ºC and are manually
reset in all versions.
The operating mechanism components are
manufactured of zinc coated steel and built into a
plastic casing.
The mechanism assembly is offset from the pivot
shaft of the slat, which allows access to the unit for
maintenance and inspection.
The Koolair fire dampers have the CE marking in
accordance with the Construction Products Directive
305/2011/EU, following the standard EN15650:2010
and classification in accordance with
EN 13501-3:2005. Also available with “NF” marking.
Option for fire dampers to be supplied with class C
air tightness in compliance with UNE-EN 1751.
Models
SCFC-PD S/UNE-EN 1366-2:2000. Circular fire
damper class:
EI-120 (ve i o) S (500 Pa) for wall,
EI-180 (ho i o) S (500 Pa) for ceiling/floor slab,
EI-120 (ve i o) S (500 Pa) for flexible wall.
Dimensions from Ø 100 to Ø 355 mm
SCFC-GD S/UNE-EN 1366-2:2000. Circular fire
damper class:
For sizes from Ø 400 to Ø 630 mm
EI-180 (ho i o) S (500 Pa) or ceiling/floor slab.
For sizes from Ø 200 to Ø 800 mm
EI-180 (ve i o) S (500 Pa) for wall.
Motor-driven circular fire dampers SCFC-PD and
SCFC-GD can be incorporated into KOOLAIR’s
KOOLCOM system for managing and monitoring fire
dampers.