Short descriptionDecentralised compact air handling unit for ceiling installation, designed for classrooms, offices and meeting rooms. Available in three sizes with air flow up to 1000 m3/h, featuring counterflow heat recovery and optional enthalpy core.
Key features- 3 sizes — up to 1000 m3/h
- Counterflow plate heat exchanger (aluminium or enthalpy), EUROVENT-certified
- Integrated CO2 sensor for demand-controlled ventilation
- Quiet operation: 35 dB(A) at 1 m (nominal speed)
- Energy-efficient EC motors and monitored filters
Efficient casing with dual insulationThe compact monobloc casing incorporates a dual-layer insulation system for thermal and acoustic performance. Outer panels: 20 mm mineral wool sandwich (λ = 0.042 W/mK). Inner layer: 30 mm melamine foam (λ = 0.034 W/mK). Back-draught shutters at outdoor and exhaust connections prevent unwanted airflow. Maintenance access via a gas-strut-supported service door.
Quiet and efficient EC fansBackward-curved centrifugal fans with EC motors provide high efficiency and low noise. Fans are statically and dynamically balanced, fitted with maintenance-free ball bearings and thermal motor protection. Integrated pressure monitoring at fan inlets enables precise airflow control.
Modular heating and cooling optionsPre- and post-heating, plus cooling, are available in electric or water-based variants. Electric heaters use SSR switching and safety thermostats with manual reset. Water coils feature copper tubes and pressed aluminium fins, rated to 100 °C and 1.6 MPa, with integrated freeze protection. Cooling versions include a condensate tray with drainage; optional condensate pump available.
Counterflow heat recoveryRemovable aluminium or enthalpy counterflow plate heat exchanger, EUROVENT-certified, with an integrated bypass damper driven by a modulating servo for accurate airflow control. Condensate is managed via an exhaust-side tray and dedicated drainage; optional pump for condensate removal.
Filters & air qualitySupply filter class: ePM1 60%. Extract filter class: Coarse 60%. Filter differential pressure is monitored by transmitters; filters are accessed and replaced via bottom service doors.
Control systemFully integrated control with 3.5" touchscreen supporting manual, CAV and DCV (demand-controlled ventilation) modes. Offers intuitive operation, automated energy-saving sequences and precise temperature regulation.
Design & applicationDesigned for under-ceiling air discharge using the Coanda effect to ensure even fresh air distribution. Suited for decentralised ventilation in classrooms, offices and conference rooms; suitable for new and existing buildings.
Operating conditionsOperation in ambient temperatures from +5 °C to +40 °C. When installed in ducting the unit is IP20. Intended for standard atmospheric air free of dust, grease and corrosive contaminants.
Technical specifications- Model: Sense CX
- Air flow: up to 1000 m3/h (3 sizes)
- Heat recovery: counterflow plate heat exchanger (aluminium or enthalpy), EUROVENT-certified
- Noise level: 35 dB(A) at 1 m (nominal speed)
- Motors: EC motors
- Fans: backward-curved centrifugal fans; statically and dynamically balanced; maintenance-free ball bearings; thermal protection; fan inlets with pressure transmitters
- Filters: Supply ePM1 60%; Extract Coarse 60%; monitored by pressure transmitters
- Casing insulation: outer 20 mm mineral wool sandwich (λ = 0.042 W/mK); inner 30 mm melamine foam (λ = 0.034 W/mK)
- Pre-/post-heater options: electric (SSR switching, safety thermostats, overheat protection) or water-based (copper tubes, aluminium fins; max 100 °C, 1.6 MPa)
- Cooling: condensate tray with drainage; optional condensate pump
- Condensate management: exhaust-side tray; dedicated drainage; optional pump
- Temperature sensors: inlet (ODA), supply (SUP), extract (ETA), exhaust (EHA); anti-freeze protection for heat recovery core and water coil
- Integrated CO2 sensor for demand control
- Control: integrated system with 3.5" touchscreen; supports CAV and DCV
- IP rating (installed in ducting): IP20