To actively detect gas and control gas valves / alarms.
may cooperate with eight gas sensors
memory of alarms generated
diode indicators continually visualize the highest gas concentration in the system monitored
battery remaining operational during power cuts for up to several hours
continuous monitoring of correct gas sensor operation
indicator / actuator testing function
units may be linked to increase system capacity
alarm warns against excessive gas concentration and cuts off gas supply
alarm signal may be transmitted to external systems
sensors protected against short circuit with semiconductor devices
inputs protected against interferences / voltage surges
conformity with harmonized standards for gas devices and with EMC / LVD Directives
Device controlled
fan, gas cut-off valve, alarm circuitry
Power supply
230 V 50 Hz
Back-up batteries
7,2 Ah gel battery
Number of gas sensors
8
Gas sensor type
4…20 mA linear current loop corresponding to 0…20 % LEL (Lower Explosion Limit)
Alarm threshold
20,3 mA ± 2 %
Fuse
1 A (slow)
Fan output
voltage-free NO contacts (rated load 3 A 230 V 50 Hz)
Alarm output
voltage-free NO contacts (rated load 3 A)
Electrically held gas
valve output12 VDC, rated load 1.3 A (16 W)
Status visualization
LED diodes
Operating temperature range
+10 °C…+30 °C
Storage temperature range
+5 °C…+40 °C
IP rating
IP 22, class II protection against electric shocks
Colour
gray
Mount method
wall-mounted, wall plugs
Weight
5,58 kg
Certificates/standards
complies with the EMC and LVD Directives, and with the PN-EN50194:2005 standard Type 2 according to the PN-EN50270:2005 standard