The central outdoor sensor unit measures the outdoor temperature and transmits this value to the controllers connected via the VBus®.
For use with the DeltaTherm® HT and FAP13
Inputs: 1 Pt1000 temperature sensor
Outputs: 1 semiconductor relay, 1 potential-free extra-low voltage relay
Technical data:
Inputs: 1 Pt1000 temperature sensor
Outputs: 1 semiconductor relay, 1 potential-free extra-low voltage relay
Switching capacity: 1 (1) A 100 –240 V~ (semiconductor relay),
1 (1) A 30 V⎓ (potential-free relay)
Total switching capacity: 2 A 240 V~
Power supply: 100–240 V~ (50–60 Hz)
Supply connection: type X attachment
Data interface: VBus®
VBus® current supply: 60 mA
Housing: plastic
Mounting: wall mounting, also suitable for mounting into patch panels
Indication/Display: 1 operating control LED
Protection type: IP 20/ EN 60529
Protection class: I
Ambient temperature: 0…40 °C
Degree of pollution: 2
Dimensions: 110 x 166 x 47 mm
The unit must only be located in dry interior rooms.
If the device is not equipped with a mains connection cable and a plug, the device must
additionally be supplied from a double pole switch with contact gap of at least 3 mm.
Please pay attention to separate routing of sensor cables and mains cables.
In order to mount the device to the wall, carry out the following steps:
Î Unscrew the crosshead screw from the cover and remove it along with the
cover from the housing.
Î Mark the upper fastening point on the wall. Drill and fasten the enclosed wall
plug and screw leaving the head protruding.
Î Hang the housing from the upper fastening point and mark the lower fastening
point (centres 130 mm).
Î Insert lower wall plug.