Fast recovery stainless steel tank-in-tank cylinder
Tank-in-Tank floor standing indirect hot water storage tank.
Stainless steel construction - no need for sacrificial anodes.
High performance - fast heat up and rapid recovery.
Low heat loss - 100mm polyurethane insulation foam
Can be used in battery formation for high output installations.
Large heating surface area means reduced boiler cycling.
Anti-Legionella : Storage temperature > 60 °C
Constructive characteristics
Capacity (total) - 1000 - L
Capacity (primary) - 160 - L
Weight (empty) - 308 - kg
Max operating temperature - 85 - °C
Max operating pressure heating (primary) - 4 - bar
Max operating pressure (DHW) - 8,6 - bar
Primary flow (EN 12897:2016) - 2,08 - L/s
Connection - primary - 2 F - Ø"
Connection - DHW - 1 ½ M - Ø"
Connection - re-circulation / safety valve - 1 ½ M - Ø"
Heating characteristics
Reheat time (EN 12897) - - - min
Reheat performance (EN 12897:2016) - 97 - kW
Max absorbed heat (Heat source: boiler) - 112 - kW
Domestic hot water performance
Peak flow at 40°C - 2265 - L/10’
Peak flow 1st hour at 40°C - 4940 - L/60’
Continuous flow at 40°C - 3210 - L/h
Peak flow at 45°C - 1941 - L/10’
Peak flow 1st hour at 45°C - 4234 - L/60’
Continuous flow at 45°C - 2751 - L/h
Peak flow at 60°C - 1145 - L/10’
Peak flow 1st hour at 60°C - 2438 - L/60’
Continuous flow at 60°C - 1562 - L/h
Coefficient (NL) - 87