Dry contact inputs
Binary inputs
LED indications
Switch outputs
Shutter control outputs
TRIAC dimming outputs
Fan coil output
0-10V drive interface as dimming outputs or fan coil output
Logic, Time and Scene group functions
Support KNXnet/IP Tunneling
Support KNXnet/IP Router
Bus voltage 21-30V DC, Via KNX/EIB
Bus current <12mA
Bus consumption <360mW
Auxiliary voltage 24-30V DC
Auxiliary current <200mA
Input 5ch Binary Input,with 5ch LED indicator
Output 25ch switch outputs(4ch is 16A, rated voltage is 250VAC; other 21ch is 6A, rated voltage is 240VAC),some channel can be also use as shutter, fan cont
Output 3ch 0-10VDC outputs, rated current is 50mA, can be used as dimming or fan coil output
Output 2ch Triac Dimming outputs, max.100W per channel